NO LOAD & LOAD TEST BENCH

These are the test benches incorporating control & measurement circuitry necessary for testing single phase as well as three phase transformers of several VA to MVA rating & voltage class of 11KV/433V,as well 33KV/11 KV, after manufacturing, repairing, reconditioning. Following tests can be done by these Test Sets.

  • No load Test from L.T. side
    Input voltage to L.T. side.
    No load current.
    No load or excitation loss.
  • Load Test
    Impedance voltage.
    Rated L.T. & H.T. current.
    Conductor loss
  • Temperature rise Test
    Injection only at equivalent short circuit current (Temperature/Time measurement scheme is available
    at extra cost).
  • Polarity
  • Phase sequence
  • Ratio error

Input: 415 volts, 3 phase 4 wire, 50Hz, AC.

Range of equipment:

TypeInput
OutputRange of transformers under test
LDNLD1P1230V, 50Hz. , single phase AC.0-240V AC at 50A
0-480V AC at 25A
0-960V AC at 12.5A
Distribution transformers from 3KVA to 250KVA i.e. 20KV primary & 480V secondary.
LDNLD3P1415V, 3phase, 4 wire, 50Hz. AC.0 to 500V, 3 phase continuously variable AC. Capacity: 28A.Distribution & Power transformers upto 500KVA.
LDNLD3P2400V, 3 phase, 4 wire, 50Hz. AC.3 phase output:
0-2.75KV AC
0-5.5KV AC
0-11KV AC
Capacity: 200KVA.
1phase output:
0-500V AC;
Capacity: 2.5KVA.
3 phase transformers-
Upto 33KV (Ph-Ph) primary voltage & Upto 11KV secondary voltage.
Capacity: 3MVA Max.
1 phase transformers- Upto 11KV primary voltage & 250V secondary voltage. Capacity: 50KVA Max.

Protection:

  • Foot switch interlock.
  • Zero start interlock.
  • Over load and short circuit.
  • A remote interlock connector to interlock the test cage area.

Metering:
High accuracy precision Digital measurement instrumentation (voltmeter, ammeter & wattmeter) scheme with metering accuracy of + 1% is incorporated. Suitable transducers are used for range transformations.

Auxiliary step up transformer:
Usually, these sets are made for 11KV/433-voltage class. However, additional step up transformers are available at extra cost to suit the test sets for 33KV/11KV class.

Apart from the existing Types, sets as per requirement of customer may also be manufactured.

Qty :

 
 
 
Home|About Us|Products|Certificates|Enquiry|Feedback|FAQ's|Contact Us
Copyright © 2010 - International Biological Laboratories. All rights reserved.
Our Associated Websites
www.interlabs-India.com | www.interlabs.in | www.interlabs.co.in | www.ambalalab.com | www.interlabs.info | www.interlabs-has.com | www.best-visibility.com | www.vidyatechnoart.com | www.labs-glassware.com | www.v-pyrex.com | www.ncert-kits.com | www.shoppingbags.com | www.pharmaceuticalgiftsanatomicalmodels.com
 